Typical distribution chain: utility feed (10kV) → HV switchgear → transformer (10kV/0.4kV) → LV switchgear → UPS → RPP/PDU → IT rack. This page estimates total power, annual energy, electricity cost and carbon from IT load and PUE.
Large AI data centers often use 2N dual feed. For high-power-density AI zones also consider per-rack PDU capacity and busway selection.
Input parameters
racks
kW/rack
Typical: standard racks 4–8 kW, high-density AI / liquid-cooled 20–100+ kW
kW
%
Servers typically run at 50%–80%; idle units still consume power
1.1 excellent1.52.5 poor
PUE = 1.50
PUE = total data-center power ÷ IT power. Regulations require new large data centers to reach PUE ≤ 1.3
Locating you…
$/kWh
Auto-matched to local commercial average tariff by IP
kgCO≡/kWh
China national grid average ≈ 0.5568 kgCO≡/kWh; adjust per region
Results
Effective IT load
— kW
Total data-center power
— kW
Annual energy
— MWh/yr
Annual electricity cost
— /yr
Annual carbon
— tCO≡/yr
Cost per rack per year (rack mode)
— /rack·yr
Power breakdown (total = 100%)
IT equipment—
Cooling (CRAC / tower)—
Power distribution losses (UPS/transformer)—
Lighting & other—
Total power = IT load × PUE
Non-IT part split by typical ratios: cooling ≈ 70%, distribution losses ≈ 25%, lighting & other ≈ 5%
PUE sensitivity (same IT load)
PUE scenario
Total power kW
Annual energy MWh
Annual cost
UPS & battery quick sizing
Auto-matches mainstream high-power 3-phase UPS and LFP smart lithium battery cabinets from the effective IT load above. Capacities are typical ratings; final selection per vendor manual. UPS capacity already includes redundancy factor and 20% design margin.
LFP smart lithium battery cabinets (capacity by backup time)
Brand / series
Recommended model
Capacity / cabinet
Cabinets
Total capacity
Footprint ref.
Note
Same basis as the “Backup Power” page: UPS capacity = IT load ÷ 0.9 × (1 + 20% margin) × redundancy factor (N+1 = 1.25, 2N splits across two buses); battery capacity = IT load × backup hours ÷ 0.94 (UPS efficiency).
Unit counts are the minimum integer combination meeting the demand; for small loads pick smaller models and verify modular scalability.
LV switchgear & ATS quick sizing
Auto-matches LV switchgear (main incoming / busbar), smart rack power panels (one per row) and ATS automatic transfer switches (mains/genset) from total power. Capacities are typical ratings; final selection per vendor manual. ATS demand links to genset capacity on the “Backup Power” page.
Total incoming current — ARPP needed — unitsATS switching current — AArchitecture
Racks per row
LV switchgear (main incoming / distribution center)
Cabinet series
Recommended type
Main busbar rating
Incoming sets
Feeder boards (ref.)
Total incoming current
Note
Smart rack power panels (rack-level distribution)
Brand / series
Recommended model
Incoming rating
Units
Row load ref.
Note
ATS transfer switches (mains ↔ genset)
Brand / series
Recommended model
Rated current
Units
Switching capacity
Note
Basis: total incoming current = total power ÷ 0.9 (apparent kVA) × 1.443 (400V 3-phase); RPP incoming rating by row load current; ATS switching current = genset kVA × 1.443 (ATS must carry full genset output).
ATS is a PC-class transfer switch (GB/T 14048.11); in a 2N architecture each bus gets one unit. Feeder board count is an estimate by rack count; final circuits need detailed design.